A high-severity improper authentication vulnerability, tracked as CVE-2025-41450, affects Danfoss AK-SM 800A Series devices (listed by NVD as the AK-SM 8xxA Series) running versions prior to 4.2. According to CISA, an attacker could exploit the flaw to generate a web report that exposes sensitive information, including internal IP addresses, usernames and store names.
The flaw carries a CVSS 3.1 base score of 7.5 (High). CISA added it to its Known Exploited Vulnerabilities (KEV) catalog on 25 November 2026, which confirms it is being exploited in the wild. Organisations running these devices should treat remediation as urgent.
What’s affected
The NVD entry lists the following as affected:
- Danfoss AK-SM 8xxA Series: all versions prior to 4.2
CISA’s KEV entry refers to the product as the AK-SM 800A Series. The NVD record does not list version 4.2 or later as affected. However, the advisory data we reviewed does not explicitly confirm which release contains the fix. Check the Danfoss advisory for the confirmed fixed version before upgrading.
How serious is it
NVD scores the flaw 7.5 (High) with the vector CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N. In plain terms:
- Attack vector: Network. It can be exploited remotely over a network.
- Attack complexity: Low. No special conditions are needed.
- Privileges required: None. The attacker does not need an account or credentials.
- User interaction: None. No one has to click or open anything.
- Confidentiality impact: High. Sensitive information can be disclosed.
- Integrity and availability impact: None. The score does not reflect any ability to modify data or disrupt the device.
The weakness is classified as CWE-305, Authentication Bypass by Primary Weakness. The impact is information disclosure rather than device takeover. Even so, leaked usernames and internal network addresses can help an attacker plan further attacks.
Is it being exploited?
Yes. CISA added CVE-2025-41450 to its KEV catalog on 25 November 2026, confirming active exploitation. CISA lists its use in ransomware campaigns as “Unknown”.
Under Binding Operational Directive 26-04, US federal civilian agencies must act by 9 December 2026. CISA’s required action is to:
- apply mitigations in accordance with vendor instructions;
- follow BOD 26-04 guidance on prioritising security updates based on risk;
- follow CISA’s “Forensics Triage Requirements”;
- follow applicable BOD 26-04 guidance for cloud services, or discontinue use of the product if mitigations are unavailable.
CISA also notes that stakeholders are responsible for evaluating each asset’s internet exposure.
The directive only binds federal agencies, but other organisations should treat the KEV listing as a strong signal to prioritise this fix.
What to do
- Inventory your devices. Identify all Danfoss AK-SM 800A/8xxA Series units and check their software versions.
- Upgrade. Move affected units off versions prior to 4.2, following the instructions in the Danfoss security advisory (DSA-2025-03-01).
- Restrict exposure. Make sure the devices’ web interfaces are not reachable from the internet. Limit access to trusted management networks, for example behind a firewall or VPN.
- Review for compromise. Because exploitation is confirmed, check whether exposed devices may already have leaked data. Consider rotating credentials for usernames that may have been exposed.
- Federal agencies should also follow BOD 26-04 and CISA’s Forensics Triage Requirements by the 9 December 2026 due date.