An improper input validation vulnerability in Danfoss AK-SM 800A Series system managers, tracked as CVE-2023-25915, could allow an authenticated remote attacker to execute arbitrary commands on the affected system. NVD lists AK-SM800A versions earlier than 3.3 as affected and rates the flaw 8.8 (High) on the CVSS 3.1 scale.
The vulnerability was published in August 2023. On 2026-11-25, the US Cybersecurity and Infrastructure Security Agency (CISA) added it to its Known Exploited Vulnerabilities (KEV) catalog, confirming that it is being exploited. Organisations running these devices should treat remediation as urgent.
What’s affected
According to the NVD record, the affected product is the Danfoss AK-SM800A, which CISA’s catalog lists as the AK-SM 800A Series. Versions earlier than 3.3 are marked as affected.
The records list affected versions as “< 3.3” but do not explicitly name a fixed release. The advisory data does not yet confirm which version contains the fix. Administrators should check the Danfoss security advisory linked below for the vendor’s stated fixed version and guidance.
How serious is it
NVD assigns a CVSS 3.1 base score of 8.8 (High), with the vector CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H. In plain terms:
- Attack vector: Network. The flaw can be exploited remotely over a network.
- Attack complexity: Low. No special conditions are needed for an attack to work.
- Privileges required: Low. The attacker needs a valid account on the device, but not necessarily an administrative one.
- User interaction: None. No action by another user is required.
- Impact: High for confidentiality, integrity and availability. Successful exploitation could give an attacker full control over the data and operation of the system.
The weakness is classified as CWE-20 (Improper Input Validation). Because it leads to arbitrary command execution, it can be used to take over the device itself. That is a serious concern for systems that may sit inside operational or building-management networks.
Is it being exploited?
Yes. CISA added CVE-2023-25915 to its KEV catalog on 2026-11-25, which means the agency has evidence of exploitation in the wild. CISA lists use in ransomware campaigns as “Unknown”. The supplied records do not give further detail about who is exploiting the flaw or how.
For US federal civilian agencies, CISA’s required action is to apply mitigations in accordance with vendor instructions. Agencies must also follow BOD 26-04 (Prioritizing Security Updates Based on Risk) and CISA’s Forensics Triage Requirements, or discontinue use of the product if mitigations are unavailable. CISA also notes that stakeholders are responsible for evaluating each asset’s internet exposure. The due date is 2026-11-28.
What to do
- Identify devices. Inventory all Danfoss AK-SM 800A Series units in your environment and record their firmware versions.
- Apply the vendor’s fix or mitigations. Follow the instructions in Danfoss advisory DSA-2023-08-01. Units running versions before 3.3 fall within the affected range, so confirm the recommended target version in the vendor advisory before upgrading.
- Restrict exposure. Make sure these controllers are not directly reachable from the internet. Limit access to trusted management networks, for example behind a firewall or VPN.
- Review accounts. Exploitation requires an authenticated user, so do two things. Remove unused accounts, change default or shared credentials, and enforce strong passwords. Then review access logs for unexpected logins.
- Check for compromise. Because the flaw is known to be exploited, look for signs of unauthorised activity on exposed or previously unpatched devices. If you are a federal agency, apply CISA’s forensics triage guidance.
- Remove the device from service if needed. If you cannot patch or mitigate, consider disconnecting or discontinuing use, as CISA advises.
References
- Danfoss security advisory DSA-2023-08-01
- DIVD CSIRT: CVE-2023-25915
- DIVD CSIRT case DIVD-2023-00025
- CISA Known Exploited Vulnerabilities catalog entry
- CISA BOD 26-04: Prioritizing Security Updates Based on Risk
- CISA BOD 26-04 implementation guidance (Forensics Triage Requirements)
- NVD: CVE-2023-25915